13 Troubleshooting
Error
code
(hex)
03D1
Ethernet advanced setting error
03D2
Packet discarded.
03D3
Link OFF error
03D4
Verification error (Tag data link only)
Note For details on identifying the cause
of the verification error, refer to 13-
3 Connection Status Codes and
Error Processing.
This error will not be stored when a
target node is missing.
03D5
Tag data link error
0601
CPU Bus Unit error
0602
CPU Bus Unit memory error
* If a memory error occurs in the error log area of the non-volatile memory, the record will not be stored in the non-volatile
memory.
13-30
Error
02 hex: FINS setting error
01 hex
00 hex
Connection instance num-
ber (0 to 255)
00 hex
Variable
01: Read error
02: Write error
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Detail code
First byte
Second byte
01 hex: Checksum error
10 hex: Invalid IP router
table
11 hex: Invalid FINS/UDP
setting
12 hex: Invalid FINS/TCP
setting
13 hex: Invalid FTP setting
14 hex: Invalid SNTP set-
ting
15 hex: Invalid SNMP set-
ting
16 hex: Invalid SNMP trap
setting
00 hex
00 hex
Lower eight bits of IP
address
Lower eight bits of IP
address
02 hex: Network parame-
ter
06 hex: Error log
09 hex: Identity data
0E hex: Unit name
0F hex: Ethernet basic
setting
10 hex: Ethernet
advanced setting
11 hex: MAC address
12 hex: Status area layout
setting
14 hex: Term Tag address
resolution memory write
error
Saved in
non-volatile
memory
Yes
No
No
No
No
Yes
Yes *