Event name
Ethernet Advanced Setting Error
Meaning
There is an illegal FINS setting.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The power was interrupted during a
download.
A communications error occurred dur-
ing a download.
Attached
None
information
Precautions/
None
Remarks
Event name
Address Mismatch
Meaning
The host ID of the local IP address is inconsistent with the FINS node address. Or, the last segment of the local IP
address is inconsistent with the setting on the node address switches.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The IP address conversion method is
set to automatic generation, but the
host ID of the local IP address is
inconsistent with the FINS node
address or the last segment of the
local IP address is inconsistent with
the setting on the node address
switch.
Attached
None
information
Precautions/
None
Remarks
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Identify the cause of the error from
the detailed information in the error
history of EtherNet/IP Unit, and then
correct the settings.
Implement noise countermeasures if
there is excessive noise.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Set the IP address or node address to
match.
13 Troubleshooting
Event code
34AF 0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
The relevant function stops.
Name
---
Prevention
Make sure that the power supply is
not interrupted during a download.
Implement noise countermeasures.
Event code
34B0 0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
FINS communications are not possible.
Name
---
Prevention
None
At power ON,
Controller reset,
or Unit restart
System
13
At power ON,
Controller reset,
or Unit restart
System
13-43