13 Troubleshooting
Event name
IP Router Table Error
Meaning
The IP router table information is incorrect.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The power was interrupted during a
download.
A communications error occurred dur-
ing a download.
Attached
None
information
Precautions/
None
Remarks
Event name
Routing Table Error
Meaning
The routing table information is incorrect.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The power was interrupted during a
download.
A communications error occurred dur-
ing a download.
Attached
None
information
Precautions/
None
Remarks
13-42
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Download the settings from the Sys-
mac Studio again.
Implement noise countermeasures if
there is excessive noise.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Download the settings from the Sys-
mac Studio again.
Implement noise countermeasures if
there is excessive noise.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Event code
34AD0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
Ethernet communications for the EtherNet/IP Unit are not
possible.
Name
---
Prevention
Make sure that the power supply is
not interrupted during a download.
Implement noise countermeasures.
Event code
34AE0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
Ethernet communications for the EtherNet/IP Unit are not
possible.
Name
---
Prevention
Make sure that the power supply is
not interrupted during a download.
Implement noise countermeasures.
At power ON,
Controller reset,
or Unit restart
System
At power ON,
Controller reset,
or Unit restart
System