13 Troubleshooting
Event name
Invalid Communications Parameter
Meaning
An error was found in the validation check of the parameters for tag data links that are saved in non-volatile memory.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The power was interrupted during a
download.
A communications error occurred dur-
ing a download.
Non-volatile memory failure
Attached
None
information
Precautions/
None
Remarks
Event name
Tag Database Error
Meaning
A tag database error occurred in the CPU Unit when using variables for tag data links, status layout, etc.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The power was interrupted during a
download.
A communications error occurred dur-
ing a download.
Attached
None
information
Precautions/
None
Remarks
13-38
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Download the device parameters
from the Network Configurator again.
Check for ambient noise. If there is a
noise source, remove it.
If the error occurs even after perform-
ing the actions described above,
replace the EtherNet/IP Unit.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Download the settings from the Sys-
mac Studio again.
Implement noise countermeasures if
there is excessive noise.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Event code
14840000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
Tag link function of the EtherNet/IP Unit cannot be used.
Name
---
Prevention
Make sure that the power supply is
not interrupted during a download.
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
None
Event code
14850000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
Tag data link function of the EtherNet/IP Unit cannot be
used.
Name
---
Prevention
Make sure that the power supply is
not interrupted during a download.
Implement noise countermeasures.
At power ON,
Controller reset,
or Unit restart
System
At power ON,
Controller reset,
or Unit restart
System