8 Message Communications
8-2-4

Route Path

The route path indicates the path from the local CPU Unit to the remote Controller on the network.
Routing is performed for CIP communications instructions based on route paths.
Route Path Notation
The EPATH data type is used to give route paths. The basic format is shown below.
Network_type_number \Remote_address
The network type number and the remote address are determined as shown in the following table
according to whether the route type is (1) a Unit on the CPU Rack or (2) a communications port on a
Communications Unit.
Route
1. Output to Unit on CPU Rack
2. Output from communications
port on Communications Unit
Unit
Backplane port
(#01)
(1) When Routing the Output to a Unit on the CPU Rack
Output the command to the backplane port as a network with the CPU Rack. Specify the
Unit address as the address of the remote Unit.
(2) When Routing the Output to a Communications Port on a Communications Unit
Output the command to an EtherNet/IP port. Specify the IP address as the address of the
remote node.
Additional Information
Unit Addresses
A Unit address is used to discriminate between several devices connected to a single node on a
network.
Set the unit address as shown below.
• CPU Unit:
• CPU Bus Units (EtherNet/IP Units):
• Special I/O Unit:
• Inner Board:
• Computer:
• The Unit connected to network:
8-6
Network type number
(hexadecimal)
#01 (backplane port)
#02 (EtherNet/IP Unit)
EtherNet/IP Unit
(1)
Communications
port (#02)
IP address
(2)
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Remote Unit address (Refer to
Additional Information below.)
IP address
00 hex
Unit number + 10 hex
Unit number + 20 hex
E1 hex
01 hex
FE hex
Remote address