Omron CJ1W-EIP21 Operation Manuals page 242

For nj-series cpu unit. cj-series ethernet/ip units
Hide thumbs Also See for CJ1W-EIP21:
Table of Contents

Advertisement

8 Message Communications
Attribute ID
Parameter name
04 hex
Interface Counters
In Octets
In Unicast Packets
In NonUnicast Packets
In Discards
In Errors
In Unknown Protos
Out Octets
Out Unicast Packets
Out NonUnicast Packets
Out Discards
Out Errors
8-36
Description
The path to the link object in the
physical layer
The number of octets received
through the interface.
This includes unnecessary multi-
cast packets and discarded pack-
ets counted by InDiscards.
The number of unicast packets
received through the interface.
This does not include discarded
packets counted by InDiscards.
The number of packets besides
unicast packets received through
the interface. This includes
unnecessary multicast packets,
but does not include discarded
packets counted by InDiscards.
The number of discarded incom-
ing packets received through the
interface.
The number of incoming packets
that had errors. This is not
included in InDiscards.
The number of incoming packets
that were of an unknown protocol.
The number of octets sent
through the interface.
The number of unicast packets
sent through the interface.
The number of packets besides
unicast packets sent through the
interface.
The number of discarded sent
packets.
The number of sent packets that
had errors.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Read/write data
Attribute
Data
type
Read
Struct
---
UDINT
Reads the current value.
UDINT
Reads the current value.
UDINT
Reads the current value.
UDINT
Reads the current value.
UDINT
Reads the current value.
UDINT
Reads the current value.
UDINT
Reads the current value.
UDINT
Reads the current value.
Read
UDINT
Reads the current value.
UDINT
Reads the current value.
UDINT
Reads the current value.
Value