13 Troubleshooting
Event name
BOOTP Server Error
Meaning
Connection with the BOOTP server failed.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Server setting error (The acquired IP
address is illegal.)
Server is down.
An error occurred in the communica-
tions path.
Attached
None
information
Precautions/
None
Remarks
Event name
Access Detected Outside Range of Variable
Meaning
Accessing a value that is out of range was detected for a tag variable that is used in a tag data link.
Source
PLC Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
An out-of-range value was written by
an EtherNet/IP tag data link for a vari-
able with a specified range. A value
that does not specify an enumerator
was written by an EtherNet/IP tag
data link for an enumeration variable.
Attached
None
information
Precautions/
• Write operations for out-of-range values or values that do not specify enumerators do not end normally.
Remarks
• Write operations for in-range values or values that specify enumerators end normally.
13-46
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
If an illegal value is set for the Ether-
Net/IP IP address in the server, cor-
rect it.
Check if the server at the remote con-
nection is operating normally and set
it to operate normally if it is not.
Check the communications path to
the server and take corrective mea-
sures if there are any problems.
Source details
Observation
Recovery
Continues.
Operation
EtherNet/IP NET ERR
---
Data type
---
Correction
Correct the value that is written to the
variable with a specified range so that
the value is in the range. Correct the
value that is written to the enumera-
tion variable so that the value speci-
fies an enumerator.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Event code
84E10000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
Requests to the BOOTP server will continue until there is
a response from the BOOTP server. During that time,
communications using BOOTP are not possible. Error
responses are returned to all communications requests.
Data refreshing with the PLC Function Module will con-
tinue. The IP address of the EtherNet/IP port that was
specified by the BOOTP server was an illegal value. Oper-
ation is performed with the illegal default IP address
(192.168.250.node_address).
Name
---
Prevention
Set the EtherNet/IP addresses in the
server so that there are no illegal val-
ues.
Check to make sure that the server at
the remote connection is operating
normally.
None
Event code
54AF0000 hex
CJ-series Unit
Detection
timing
---
Log category
Not affected.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
Write values that are in range for vari-
ables with specified ranges. Write val-
ues that specify enumerators to
enumeration variables.
After link is
established
System
When variable is
written
System