Route Path Notation Examples
The notation of the route path is different for communications on the built-in EtherNet/IP port and for
communication on an EtherNet/IP Unit. This section provides examples of route paths.
 Communicating with an EtherNet/IP Unit
Example: Communicating from the EtherNet/IP Unit mounted to CPU Unit 1 to CPU Unit 2 via the
EtherNet/ IP Unit mounted to CPU Unit 2
CPU Unit 1
Backplane port (#01)
(1) CPU Unit 1 to EtherNet/IP Unit 1
• Network type number: "01" (Output the command via internal backplane port.)
• Remote address: "#01" (unit address of EtherNet/IP Unit)
(2) EtherNet/IP Unit 1 to EtherNet/IP Unit 2
• Network type number: "02" (Output the command via EtherNet/IP port.)
• Remote address: Specify the remote IP address.
(3) EtherNet/IP Unit 2 to CPU Unit 2
• Network type number: "01" (Output the command via internal backplane port.)
• Remote address: "#00" (unit address of CPU Unit)
 Communicating with a Built-in EtherNet/IP Port
Example: Communicating from the EtherNet/ IP Unit mounted to CPU Unit 1 to CPU Unit 2 via the
Built-in EtherNet/ IP port on CPU Unit 2
CPU Unit 1
Backplane port (#01)
(1) CPU Unit 1 to EtherNet/IP Unit 1
• Network type number: "01" (Output the command via internal backplane port.)
• Remote address: "#01" (unit address of EtherNet/IP Unit)
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
EtherNet/IP
Unit 1
Unit address:
01 hex
Communications
port (#02)
Route path: \01\#01\02\192.168.250.2\01\#00
(1)
EtherNet/IP
Unit 1
Unit address:
01 hex
Communications
port (#02)
8 Message Communications
CPU Unit 2
EtherNet/IP Unit 2
Unit address:
Backplane
00 hex
port (#01)
(2)
(3)
CPU Unit 2
IP address:
192.168.250.2
Built-in
EtherNet/IP port
IP address:
192.168.250.2
EtherNet/IP
port
8-7