Event name
IP Address Duplication Error
Meaning
The same IP address is used more than once.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The IP address of the EtherNet/IP
port is also used as the IP address of
another node.
Attached
None
information
Precautions/
None
Remarks
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Perform either of the following and
then cycle the power supply to the
Controller or reset the Controller.
• Check the IP addresses of other
nodes and correct the IP address
settings so that the same address is
not used by more than one node.
• Remove the node that has the
duplicate IP address from the net-
work.
13 Troubleshooting
Event code
84E0 0000 hex
CJ-series Unit
Detection
timing
Error reset
Log category
EtherNet/IP communications are not possible. Error
responses are returned to all communications requests.
Data refreshing with the PLC Function Module will con-
tinue.
Name
---
Prevention
Perform allocations so that IP
addresses of nodes on the network
are used for only one node.
After determining
IP addresses
System