Omron CJ1W-EIP21 Operation Manuals page 165

For nj-series cpu unit. cj-series ethernet/ip units
Hide thumbs Also See for CJ1W-EIP21:
Table of Contents

Advertisement

The settings are as follows:
Setting
Connection I/O Type
Connection Type
The Connection Structure Area and the following items are not displayed if the Hide Detail Button is clicked.
Packet Interval (RPI)
Timeout Value
Connection Name
2
After you make all of the settings, click the OK Button.
 Editing Settings for All Connections
You can edit the connection settings between the originator and all of the target devices selected in
the Register Device List together in a table.
1
Click the Connections Tab, and then click the Edit All Button. The following Edit All Connec-
tions Dialog Box is displayed.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Select Input Only (tag type) to use tag data links with a CS1W-EIP21, CJ1W-
EIP21, CJ2B-EIP21, CJ2M-EIP21, CJ1W-EIP21 (CJ2), CJ1W-EIP21 (NJ),
NJ301-@@@@, or NJ501-@@@@. When you create tag data links for other
devices, select the connection I/O type specified in that device's EDS file. Use
the Input Only (ID type) setting when another company's node is the originator
and does not support connection settings with a Tag type setting.
Select whether the data is sent in multi-cast or unicast (point-to-point) format.
The default setting is multi-cast.
• Multi-cast connection:
• Point-to-Point connection:
Note Refer to 7-1-4 Overview of Operation for details on using multi-cast and
unicast connections, and counting the number of connections.
Set the data update cycle (i.e., the packet interval) of each connection
between the originator and target.
You can set an interval to between 0.5 and 10,000 ms in 0.5-ms increments
(NJ-series Controllers: between 10 and 10,000 ms in 1-ms increments).
The default setting is 50 ms (i.e., data is updated once every 50 ms).
Set the time until a connection timeout is detected. The timeout value is set as
a multiple of the packet interval (RPI) and can be set to 4, 8, 16, 32, 64, 128,
256, or 512 times the packet interval. The default setting is 4 times the packet
interval (RPI).
Set a name for the connection. (32 single-byte characters max.)
7 Tag Data Link Functions
Description
Select when the same data is shared by multi-
ple nodes. This setting is usually used.
Select when the same data is not shared by
multiple nodes. In a unicast transmission,
other nodes are not burdened with an unnec-
essary load.
7
7-35