13 Troubleshooting
Connection status
General
Additional
Status
(hex)
01
0115
01
0116
01
0117
01
011A
13-22
Source of error
Status
(hex)
Error code returned from tar-
get:
The Product Type did not
match when opening connec-
tion.
Error code returned from tar-
get:
The Major/Minor Revisions
did not match when opening
connection.
Error code returned from tar-
get:
The tag set specified in the
connection's target variables
does not exist.
Error code returned from orig-
inator:
Connection could not be
established because the buf-
fer was full due to high traffic.
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Handling
Configuration
Configuration
1
2
This error does
Depends on
not occur.
the target's
specifications.
(Contact the
target device's
manufacturer.)
Confirm that
the target
device's EDS
file is correct.
Check the
Depends on
major and
the target's
minor revisions
specifications.
set for the tar-
(Contact the
get device and
target device's
connection. If
manufacturer.)
necessary,
Confirm that
obtain the EDS
the target
file and set it
device's EDS
again.
file is correct.
Check whether
Depends on
the originator
the target's
and target tag
specifications.
sets and tags
(Contact the
are set cor-
target device's
rectly.
manufacturer.)
Check the set-
tings of the
variables in the
CPU Unit.
An unexpected
An unexpected
network load
network load
may have been
may have been
received. Use
received. Use
the Network
the Network
Configurator
Configurator
Device Monitor
Device Monitor
or the Ethernet
or the Ethernet
Tab Page to
Tab Page to
check the
check the
bandwidth
bandwidth
usage, and cor-
usage, and cor-
rect the load. If
rect the load. If
there are
there are
places where
places where
broadcast
broadcast
storms occur,
storms occur,
such as loop
such as loop
connections in
connections in
the network
the network
connection for-
connection for-
mat, then cor-
mat, then cor-
rect them.
rect them.
Configuration
2
Check the origi-
nator's connec-
tion settings.
Check the origi-
nator's connec-
tion settings.
Check the origi-
nator's connec-
tion settings.
Check whether
the target's tag
sets and tags
are set cor-
rectly.
Check the set-
tings of the
variables in the
CPU Unit.
Follow the
operating spec-
ifications for the
originator.
(Consult the
originator man-
ufacturer.)