Control Data
Device
Item
System area
[0]
s2
Completion status
[1]
s2
Connection information
Device
Item
[0]
d
Destination IP address
[1]
d
Destination port No.
[2]
d
Host station port No.
[3]
d
Application setting area
[4]
d
Precautions
Use the Built-in Ethernet port QCPU of which the function version is B or later and the first five
digits of the serial number are '11012' or higher.
Setting data
The instruction application status is stored.
0
: Normal completion
Other than 0
: Error completion (error code)
Setting data
The IP address of the external device is stored.
The port number of the external device is stored.
The port number of the host station is stored.
b15 b14 b13
to
b10 b9 b8 b7
d
+4
3
0
2
Communication method (protocol)
0: TCP/IP
1: UDP/IP
With/without procedure in socket communication function
1: Nonprocedural communication
Open system
00: Active open or UDP/IP
10: Unpassive open
11: Fullpassive open
to
b0
1
0
7.6 SOCCINF Instruction
SP_SOCCINF
Setting range
Setting side
System
Setting range
Setting side
1
to
H
FFFFFFFF
H
0
: No
H
System
destination
(FFFFFFFF
:
H
broadcast)
1
to FFFF
H
H
(FFFF
:
System
H
broadcast)
1
to 1387
,
H
H
1392
to
System
H
FFFE
H
(See the left
System
column.)
7-17