5.4.10

RSTOP instruction

Z(P)_RSTOP_J
Z(P)_RSTOP_U
Structured ladder
Z_RSTOP_J
Z_RSTOP_U
EN
ENO
EN
Jn*
d
Un*
n1
n1
n2
n2
n3
n3
n4
n4
Input argument
EN:
Executing condition
Jn*:
Network number of the host station (1 to 239)
254: Network specified in
access
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in
three digits)
n1:
Channel used by host station
n2:
Target station number
n3:
Target station's CPU type
n4:
Mode
Output argument
ENO:
Execution result
d:
Variable that turns ON upon completion of the instruction
d[1] also turns ON at the time of error completion.
Setting
data
5.4 CC-Link IE Controller Network, MELSECNET/H, and Ethernet Instruction
ST
ENO
ENO:=
(EN, Jn*, n1, n2, n3, n4, d);
Z_RSTOP_J
d
ENO:=
(EN, Un*, n1, n2, n3, n4, d);
Z_RSTOP_U
"
Valid module during other station
"
Internal device
R, ZR
*1
Bit
Word
n1
n2
n3
n4
d
*1: Local devices and file registers per program cannot be used as setting data.
Z_RSTOP_J, Z_RSTOP_U
Z_RSTOP_J, Z_RSTOP_U
P: Executing condition
indicates any of the following
instructions.
Z_RSTOP_J
Z_RSTOP_U
:Bit
:String
:String
:ANY16
:ANY16
:ANY16
:ANY16
:Bit
:Array of bit [0..1]
J
\
U
\G
Bit
Word
5.4.10 RSTOP instruction
CC IE
NET/H
:
ZP_RSTOP_J
ZP_RSTOP_U
5
Constant
Zn
Others
K, H
5-183

Advertisement