Mitsubishi MELSEC-L series Programming Manual page 336

Hide thumbs Also See for MELSEC-L series:
Table of Contents

Advertisement

SP_SOCSND
Control Data
Device
Item
System area
[0]
s2
Completion status
[1]
s2
Send Data
Device
Item
Send data length
[0]
s3
[1]
s3
to
Send data
[n]
s3
Precautions
Use the Built-in Ethernet port QCPU of which the function version is B or later and the first five
digits of the serial number are '11012' or higher.
7.5 SOCSND Instruction
7-14
Setting data
The instruction completion status is stored.
0
: Normal completion
Other than 0
: Error completion (error code)
Setting data
Specify the data length of the send data.
(number of bytes)
Specify the send data.
Setting range
Setting side
System
Setting range
Setting side
1 to 2046
User
User