Mitsubishi MELSEC-L series Programming Manual page 177

Hide thumbs Also See for MELSEC-L series:
Table of Contents

Advertisement

Control Data
Device
Item
Completion status
[0]
s1
Setting flag
[1]
s1
Number of connected
[2]
s1
modules
Number of retries
[3]
s1
Number of automatic
[4]
s1
return modules
Operation specification
[5]
s1
when CPU is down
Scan mode specification
[6]
s1
Delay time specification
[7]
s1
*1 :
*2 :
The instruction completion status is stored.
0
: Normal completion
Other than 0
: Error completion (error code)
Specify the validity of each setting data from
*1
0: Invalid
1: Valid
b13
b15 b14
b4
b3 b2 b1 b0
0 to 0
Error invalid station specification data
Send/receive and auto-refresh buffer
Mode
00: Remote net (Ver. 1 mode)
01: Remote net (Additional mode)
10: Remote net (Ver. 2 mode)
11: Cannot be used
Set the number of connected slave stations.
Set the number of retries to be performed to a communication error
station.
Set the number of slave stations that can be returned in one link scan.
Specify the data link status when a master station programmable
controller CPU error occurs.
0: Stop
1: Continue
Specify the link scan mode for sequence scan.
0: Synchronous
1: Asynchronous
Set '0' for the delay time.
For the setting data for which invalid is specified, default parameter is applied.
Setting a value outside the setting range results in error completion of the instruction.
Setting data
to
.
s5
s2
Slave station setting data
s2
Reserved station specification data
s3
s4
assignment data
s5
5.3 CC-Link Instruction
5.3.7 RLPASET instruction
G_RLPASET
Setting range
Setting side
*2
System
User
1 to 64
User
1 to 7
User
1 to 10
User
0, 1
User
0, 1
User
0
User
5-131
5