F1-37
PG 2 Signal Selection
(3BD)
<1> Default setting is determined by parameter A1-02, Control Method Selection.
u

F2: Analog Input Card (AI-A3)

No.
(Addr.
Name
Hex)
F2-01
Analog Input Option Card
(38F)
Operation Selection
F2-02
Analog Input Option Card
(368)
Gain
F2-03
Analog Input Option Card
(369)
Bias
u

F3: Digital Input Card (DI-A3)

No.
(Addr.
Name
Hex)
F3-01
Digital Input Option Card
(390)
Input Selection
F3-03
Digital Input Option DI-A3
(3B9)
Data Length Selection
u

F4: Analog Monitor Card (AO-A3)

No.
(Addr.
Name
Hex)
F4-01
Terminal V1 Monitor
(391)
Selection
F4-02
(392)
Terminal V1 Monitor Gain
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
V/f
V/f w PG
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: A pulse detection
1: AB pulse detection
Description
All Modes
0: Option card input terminals V1, V2, and V3 replace drive input terminals
A1, A2, and A3.
1: Input signals to terminals V1, V2, and V3 are added together to create the
frequency reference.
All Modes
Sets the gain for the input signal to the analog card.
All Modes
Sets the bias for the input signal to the analog card.
Description
All Modes
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5-digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hertz or user-set units
(o1-03 = 2 or 3), the units for F3-01 are determined by parameter o1-03.
All Modes
0: 8 bit
1: 12 bit
2: 16 bit
Description
All Modes
Sets the monitor signal for output from terminal V1. Set this parameter to the
last three digits of the desired Uo-oo monitor. Some U parameters are
available only in certain control modes.
All Modes
Sets the gain for voltage output via terminal V1.
CLV
A.8 F: Options
Values
Page
Default: 0
86
Range: 0, 1
Values
Page
Default: 0
86
Range: 0, 1
Default: 100.0%
Min.: -999.9
87
Max.: 999.9
Default: 0.0%
Min.: -999.9
87
Max.: 999.9
Values
Page
Default: 0
87
Range: 0 to 7
Default: 2
87
Range: 0 to 2
Values
Page
Default: 102
88
Range: 000 to 999
Default: 100.0%
Min.: -999.9
88
Max.: 999.9