V/F Pattern Default Values; V/F Pattern Default Values - YASKAWA A1000 HHP Programming Manual

High performance vector control drive
Table of Contents

Advertisement

A.17 V/f Pattern Default Values
The following table shows the V/f pattern setting default values depending on the control mode (A1-02) and the V/f pattern
selection (E1-03 in V/f Control) for all HHP models:
• 400 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
• 575 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
• 690 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty.
No.
Unit
E1-03
-
0
1
E1-04
Hz
50.0
60.0
E1-05
V
400.0
400.0
<3>
E1-06
Hz
50.0
60.0
E1-07
Hz
2.5
3.0
E1-08
V
24.0
24.0
<3>
E1-09
Hz
1.3
1.5
E1-10
V
12.0
12.0
<3>
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<3> Values shown here are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690
V class drives.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table A.4 E1-03 V/f Pattern Settings for Drive Capacity:
2
3
4
5
6
60.0
72.0
50.0
50.0
60.0
400.0
400.0
400.0
400.0
400.0
50.0
60.0
50.0
50.0
60.0
3.0
3.0
25.0
25.0
30.0
24.0
24.0
70.0
100.0
70.0
1.5
1.5
1.3
1.3
1.5
12.0
12.0
10.0
12.0
10.0
V/f Control
7
8
9
A
B
60.0
50.0
50.0
60.0
60.0
400.0
400.0
400.0
400.0
400.0
60.0
50.0
50.0
60.0
60.0
30.0
2.5
2.5
3.0
3.0
100.0
30.0
40.0
30.0
40.0
1.5
1.3
1.3
1.5
1.5
12.0
14.0
18.0
14.0
22.0
A.17 V/f Pattern Default Values
OLV
F
C
D
E
<1>
90.0
120.0
150.0
60.0
60.0
400.0
400.0
400.0
460.0
460.0
60.0
60.0
60.0
60.0
60.0
3.0
3.0
3.0
3.0
3.0
24.0
24.0
24.0
27.6
25.4
1.5
1.5
1.5
1.5
0.5
12.0
12.0
12.0
13.8
4.6
CLV
60.0
460.0
60.0
0.0
0.0
0.0
0.0
A
309

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents