A.7 E: Motor Parameters
u

E1: V/f Pattern for Motor 1

No.
(Addr.
Name
Hex)
E1-01
Input Voltage Setting
(300)
E1-03
V/f Pattern Selection
(302)
E1-04
Maximum Output
(303)
Frequency
E1-05
Maximum Voltage
(304)
E1-06
Base Frequency
(305)
E1-07
Middle Output Frequency
(306)
E1-08
Middle Output Frequency
(307)
Voltage
E1-09
Minimum Output Frequency
(308)
E1-10
Minimum Output Frequency
(309)
Voltage
E1-11
(30A)
Middle Output Frequency 2
<9>
E1-12
Middle Output Frequency
(30B)
Voltage 2
<9>
E1-13
Base Voltage
(30C)
<1> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 600 V class and 690 V class drives.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
All Modes
This parameter must be set to the power supply voltage.
WARNING! Electrical Shock Hazard. Drive input voltage (not motor
voltage) must be set in E1-01 for the protective features of the drive to
function properly. Failure to do so may result in equipment damage
and/or death or personal injury.
V/f
V/f
V/f w PG
V/f w PG
OLV
OLV
OLV/PM
AOLV/PM
CLV/PM
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f, E1-04 through E1-13 settings define the V/f pattern
All Modes
These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E1-07 and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
Note:
Some parameters may not be available depending on the control
mode.
• E1-07, E1-08, and E1-10 are available only in the following control modes:
V/f Control, V/f with PG, Open Loop Vector.
• E1-11, E1-12, and E1-13 are available only in the following control modes:
V/f Control, V/f with PG, Open Loop Vector, Closed Loop Vector.
CLV
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
A.7 E: Motor Parameters
Values
Page
<1>
Default: 460 V
Min.: 310
74
<1>
Max.: 510
<2>
Default: F
Range: 0 to 9;
74
<3>
A to F
<4>
Default:
76
Min.: 40.0
Max.: 150.0
<4>
Default:
Min.: 0.0 V
76
<1>
Max.: 510.0 V
<4>
Default:
76
Min.: 0.0
Max.: 150.0
<4>
Default:
76
Min.: 0.0
Max.: 150.0
<4>
Default:
Min.: 0.0 V
76
<1>
Max.: 510.0 V
<4>
Default:
76
Min.: 0.0
Max.: 150.0
<4>
Default:
Min.: 0.0 V
76
<1>
Max.: 510.0 V
Default: 0.0 Hz
Min.: 0.0
76
Max.: 150.0
Default: 0.0 V
Min.: 0.0
76
<1>
Max.: 510.0 V
<8>
Default: 0.0 V
Min.: 0.0
76
<1>
Max.: 510.0 V
257