A.9 H Parameters: Multi-Function Terminals
No.
(Addr.
Name
Hex)
H5-04
Stopping Method after
(428)
Communication Error (CE)
H5-05
Communication Fault
(429)
Detection Selection
H5-06
Drive Transmit Wait Time
(42A)
H5-07
RTS Control Selection
(42B)
H5-09
CE Detection Time
(435)
Unit Selection for
H5-10
MEMOBUS/Modbus
(436)
Register 0025H
H5-11
Communications ENTER
(43C)
Function Selection
H5-12
Run Command Method
(43D)
Selection
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
u

H6: Pulse Train Input/Output

No.
(Addr.
Name
Hex)
H6-01
Pulse Train Input Terminal
(42C)
RP Function Selection
H6-02
(42D)
Pulse Train Input Scaling
H6-03
(42E)
Pulse Train Input Gain
H6-04
(42F)
Pulse Train Input Bias
H6-05
(430)
Pulse Train Input Filter Time
280
All Modes
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
All Modes
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault
will occur.
All Modes
Set the wait time between receiving and sending data.
All Modes
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
All Modes
Sets the time required to detect a communications error.
Adjustment may be needed when networking several drives.
All Modes
0: 0.1 V units
1: 1 V units
All Modes
0: Drive requires an Enter command before accepting any changes to
parameter settings.
1: Parameter changes are activated immediately without the Enter command
(same as V7).
All Modes
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
All Modes
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1
in V/f Control)
All Modes
Sets the terminal RP input signal frequency that is equal to 100% of the value
selected in H6-01.
All Modes
Sets the level of the value selected in H6-01 when a frequency with the value
set in H6-02 is input.
All Modes
Sets the level of the value selected in H6-01 when 0 Hz is input.
All Modes
Sets the pulse train input filter time constant.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
Description
Values
Page
Default: 0
123
Range: 0 to 3
Default: 0
123
Range: 0, 1
Default: 5 ms
Min.: 5
123
Max.: 65
Default: 1
124
Range: 0, 1
Default: 2.0 s
Min.: 0.0
124
Max.: 10.0
Default: 0
124
Range: 0, 1
Default: 1
124
Range: 0, 1
Default: 0
124
Range: 0, 1
Values
Page
Default: 0
125
Range: 0 to 3
Default: 1440 Hz
Min.: 1000
126
Max.: 32000
Default: 100.0%
Min.: 0.0
126
Max.: 1000.0
Default: 0.0%
Min.: -100.0
126
Max.: 100.0
Default: 0.10 s
Min.: 0.00
126
Max.: 2.00