F2: Analog Input Card Settings - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.6 F: Option Settings
F1-20, F1-36: PG Option Card Disconnect Detection
Sets whether the drive detects a fault or not when a PG-X3 card is disconnected.
No.
F1-20
PG Option Card Disconnection Detection 1
F1-36
PG Option Card Disconnection Detection 2
Setting 0: Disabled
Setting 1: Enabled
F1-30: PG Option Card Port for Motor 2 Selection
Specifies the drive port for the PG option card used for motor 2. This parameter should be set when switching between
motor 1 and motor 2, where both motors supply a speed feedback signal to the drive. If the same PG card is being used
for feedback signals from both motors, then set F1-30 to 0. If each motor has its own PG card connected to the drive, then
set F1-30 to 1.
Note: The motor 2 selection function cannot be used when PM motor is used.
No.
F1-30
Setting 0: CN5-C
Setting 1: CN5-B

◆ F2: Analog Input Card Settings

These parameters are used to setup the drive for operation with the analog input option card AI-A3. This section
describes parameters that govern operation with an input option card. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
F2-01: Analog Input Option Card Operation Selection
Determines how the input terminals on the AI-A3 option card are to be used.
No.
F2-01
Setting 0: Separate functions for each terminal (V1, V2 replace analog inputs 1, 2
Apply this setting to replace the drive analog input 1 and 2 by the option board terminals V1 and V2. Functions, gain, and
bias levels for an analog reference supplied by AI-A3 are set using the H3-
04: Analog Input 1 Gain and Bias Settings on page
Note: Parameter setting error oPE05 will occur if option card terminals are set for separate input functions (F2-01 = 0) while b1-01 = 3.
Setting 1: Combine input terminal values to create frequency reference
With this setting, all three input signals on the AI-A3 option card are added together to create the frequency reference.
When the option card is the source of the frequency reference for the drive, parameter b1-01 must be set to 3. Gain and
bias settings for the frequency reference supplied from AI-A3 can be set using parameters F2-02 and F2-03.
F2-02, F2-03: Analog Input Option Card Gain, Bias
Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the
combined input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
No.
F2-02
F2-03
Note: Enabled only when F2-01 = 1.
160
Parameter Name
Parameter Name
PG Option Card Port for Motor 2 Selection
Parameter Name
Analog Input Option Card Operation Selection
Parameter Name
Analog Input Option Card Gain
Analog Input Option Card Bias
Option Port
CN5-C
0, 1
CN5-B
0, 1
0, 1
0, 1
188.
-999.9 to 999.9%
-999.9 to 999.9%
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Setting Range
1
1
Setting Range
1
Setting Range
0
parameters as described in
Setting Range
100.0%
0.0%
Default
Default
Default
H3-03, H3-
Default

Advertisement

Table of Contents
loading

Table of Contents