D7: Offset Frequency - YASKAWA A1000 HHP Programming Manual

High performance vector control drive
Table of Contents

Advertisement

A.6 d: References
No.
(Addr
Name
Hex.)
d6-06
Field Forcing Limit
(2A5)
u

d7: Offset Frequency

No.
(Addr.
Name
Hex)
d7-01
(2B2)
Offset Frequency 1
d7-02
(2B3)
Offset Frequency 2
d7-03
(2B4)
Offset Frequency 3
256
V/f
V/f w PG
OLV
OLV
OLV/PM
AOLV/PM
CLV/PM
Sets the upper limit of the excitation current command during magnetic field
forcing. A setting of 100% is equal to motor no-load current. Disabled only
during DC Injection Braking.
All Modes
Added to the frequency reference when the digital input "Frequency offset 1"
(H1-oo = 44) is switched on.
All Modes
Added to the frequency reference when the digital input "Frequency offset 2"
(H1-oo = 45) is switched on.
All Modes
Added to the frequency reference when the digital input "Frequency offset 3"
(H1-oo = 46) is switched on.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
CLV
CLV
Description
Values
Page
Default: 400%
Min.: 100
73
Max.: 400
Setting
Page
Default: 0.0%
Min.: -100.0
73
Max.: 100.0
Default: 0.0%
Min.: -100.0
73
Max.: 100.0
Default: 0.0%
Min.: -100.0
73
Max.: 100.0