O3: Copy Function; O4: Maintenance Monitor Settings - YASKAWA A1000 HHP Programming Manual

High performance vector control drive
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
o2-05
Frequency Reference
(509)
Setting Method Selection
Operation Selection when
o2-06
Digital Operator is
(50A)
Disconnected
o2-07
Motor Direction at Power
(527)
Up when Using Operator
o2-09
(50D)
u

o3: Copy Function

No.
(Addr.
Name
Hex)
o3-01
Copy Function Selection
(515)
o3-02
Copy Allowed Selection
(516)
u

o4: Maintenance Monitor Settings

No.
(Addr.
Name
Hex)
o4-01
Cumulative Operation Time
(50B)
Setting
o4-02
Cumulative Operation Time
(50C)
Selection
o4-03
Cooling Fan Operation Time
(50E)
Setting
o4-05
Capacitor Maintenance
(51D)
Setting
o4-07
DC Bus Pre-Charge Relay
(523)
Maintenance Setting
o4-09
IGBT Maintenance Setting
(525)
o4-11
U2, U3 Initialization
(510)
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
All Modes
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using
the up and down arrow keys only.
All Modes
0: The drive continues operating if the digital operator is disconnected.
1: An oPr fault is triggered and the motor coasts to stop.
All Modes
0: Forward
1: Reverse
This parameter requires assigning drive operation to the digital operator.
Factory use.
Description
All Modes
0: No action
1: Read parameters from the drive, saving them onto the digital operator.
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data saved
on the operator.
All Modes
0: Read operation prohibited
1: Read operation allowed
Description
All Modes
Sets the value for the cumulative operation time of the drive in units of 10 h.
All Modes
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
All Modes
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
All Modes
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.
All Modes
Sets the value of the Maintenance Monitor for the soft charge bypass relay.
See U4-06 to check when the bypass relay may need to be replaced.
All Modes
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 for IGBT
replacement times.
All Modes
0: U2-oo and U3-oo monitor data is not reset when the drive is initialized
(A1-03).
1: U2-oo and U3-oo monitor data is reset when the drive is initialized
(A1-03).
A.12 o: Operator-Related Settings
Values
Default: 0
Range: 0, 1
Default: 1
Range: 0, 1
Default: 0
Range: 0, 1
Values
Default: 0
Range: 0 to 3
Default: 0
Range: 0, 1
Values
Default: 0 h
Min.: 0
Max.: 9999
Default: 0
Range: 0, 1
Default: 0 h
Min.: 0
Max.: 9999
Default: 0%
Min.: 0
Max.: 150
Default: 0%
Min.: 0
Max.: 150
Default: 0%
Min.: 0
Max.: 150
Default: 0
Range: 0, 1
Page
163
164
164
Page
164
164
Page
165
165
165
165
165
166
166
A
293