b1-16
Run Command
(1C5)
Selection 2
b1-17
Run Command at Power Up
(1C6)
<1> Settings 2 and 3 are not available in CLV.
u

b2: DC Injection Braking and Short Circuit Braking

No.
(Addr.
Name
Hex)
b2-01
DC Injection Braking Start
(189)
Frequency
b2-02
DC Injection Braking
(18A)
Current
b2-03
DC Injection Braking Time
(18B)
at Start
b2-04
DC Injection Braking Time
(18C)
at Stop
b2-08
Magnetic Flux
(190)
Compensation Value
<1> Default setting is determined by parameter A1-02, Control Method Selection.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
All Modes
Enabled when a terminal set for "External reference" (H1-oo = 2) closes.
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
All Modes
0: Disregarded. A new Run command must be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command
is already enabled.
Description
All Modes
Sets the frequency at which DC Injection Braking starts when "Ramp to stop"
(b1-03 = 0) is selected.
V/f
V/f
V/f w PG
V/f w PG
OLV
OLV
OLV/PM
OLV/PM
AOLV/PM
CLV/PM
Sets the DC Injection Braking current as a percentage of the drive rated current.
V/f
V/f
V/f
V/f
V/f w PG
V/f w PG
V/f w PG
V/f w PG
OLV
OLV
OLV
OLV
OLV/PM
OLV/PM
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
CLV/PM
CLV/PM
Sets DC Injection Braking (Zero Speed Control when in CLV and CLV/PM)
time at start. Disabled when set to 0.00 seconds.
V/f
V/f
V/f
V/f
V/f w PG
V/f w PG
V/f w PG
V/f w PG
OLV
OLV
OLV
OLV
OLV/PM
OLV/PM
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
CLV/PM
CLV/PM
Sets DC Injection Braking (Zero Speed Control when in CLV and CLV/PM)
time at stop.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Sets the magnetic flux compensation as a percentage of the no-load current
value (E2-03).
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
A.4 b: Application
Values
Page
Default: 0
25
Range: 0 to 3
Default: 0
25
Range: 0, 1
Values
Page
<1>
Default:
25
Min.: 0.0 Hz
Max.: 10.0 Hz
Default: 50%
Min.: 0
26
Max.: 100
Default: 0.00 s
Min.: 0.00
26
Max.: 10.00
<1>
Default:
26
Min.: 0.00 s
Max.: 10.00 s
Default: 0%
Min.: 0
27
Max.: 1000
241