F2: Analog Input Option - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

No.
Name
(Hex.)
F1-37
PG 2 Signal
Selection
(03BD)
F1-50
Encoder Selection
(03D2)
F1-51
PGoH Detection
Level
(03D3)
F1-52
Serial Encoder
Communication
(03D4)
bps

F2: Analog Input Option

No.
Name
(Hex.)
F2-01
Analog Input
Function Selection Selects the input method for the analog reference used with AI-A3.
(038F)
F2-02
Analog Input
Option Card Gain
(0368)
RUN
F2-03
Analog Input
Option Card Bias
(0369)
RUN
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Selects the type of pulse signal (channel) used for the encoder
option card. This parameter is for motor 2.
0 : A pulse detection
1 : AB pulse detection
V/f
CL-V/f
OLV
CLV
AOLV
Selects the encoder connected to PG-F3.
0 : EnDat Sin/Cos
1 : EnDat Serial Only
2 : Hiperface
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for PGoH [PG
Hardware Fault] of PG-F3 as a percentage when XXX is 100%.
Note:
This function is enabled when F1-20 = 1 [PG Hardware
Disconnection Detection Selection = Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
Selects the speed of communication between the PG-F3 and serial
encoder.
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps
Description
V/f
CL-V/f
OLV
CLV
AOLV
0 : 3 channel individual
1 : 3 channel addition
V/f
CL-V/f
OLV
CLV
AOLV
Sets the analog reference gain as a percentage when the maximum
output frequency is 100%.
Note:
This parameter is only enabled when F2-01 = 1 [Analog Input
Function Selection = 3 channel addition].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the analog reference bias as a percentage when the maximum
output frequency is 100%.
Note:
This parameter is only enabled when F2-01 = 1 [Analog Input
Function Selection = 3 channel addition].
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.9 F: Options
Default
Ref.
(Range)
0
717
(0, 1)
0
718
(0 - 2)
80%
718
(1 - 100%)
0
718
(0 - 2)
Default
Ref.
(Range)
0
718
(0, 1)
100.0%
720
(-999.9 - +999.9%)
0.0%
720
(-999.9 - +999.9%)
431
10

Advertisement

Table of Contents
loading

Table of Contents