B.5 Drive Operations by MEMOBUS/Modbus
B.5 Drive Operations by MEMOBUS/Modbus
The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings. This
section explains the functions that can be used and related parameter settings.
u

Observing the Drive Operation

A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter
settings (except for H5-ooparameters):
• observe drive status and drive control terminal status from a PLC.
• read and write parameters.
• set and reset faults.
• set multi-function inputs.
Note:
Input settings from the input terminals (S1 to S8) and from MEMOBUS/Modbus communications are both linked by a logical OR operation.
u

Controlling the Drive

Select an external reference and adjust the parameters in
reference using MEMOBUS/Modbus communications.
Reference Source
External Reference 1
External Reference 2
Refer to b1-01: Frequency Reference Selection 1 on page 18
for details on external reference parameter selections.
instructions on selecting external references 1 and 2.
322
Table B.1 Setting Parameters for Drive Control from MEMOBUS/Modbus
Parameter
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-15
Frequency Reference Selection 2
b1-16
Run Command Selection 2
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table B.1
accordingly to start and stop the drive or set the frequency
Name
and
Refer to b1-02: Run Command Selection 1 on page 19
Refer to Setting 2: External Reference 1/2 Selection on page 97
Required Setting
2
2
2
2
for