1.5 E: Motor Parameters
Set the Motor Mechanical Loss
Only required in Closed Loop Vector Control. The drive compensates for the degree of mechanical loss with torque
compensation. Although E2-09 rarely needs to be changed, adjustment may be necessary in the following circumstances:
• When there is a large amount of torque loss due to motor bearing friction.
• When there is a large amount of torque loss in a fan or pump application.
Set the Motor Iron Loss for Torque Compensation
Only required when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to improve the precision
of torque compensation.
u

E3: V/f Pattern for Motor 2

These parameters set the V/f pattern used for motor 2.
switching motors.
Note:
The function for switching between two motors cannot be used with a PM motor. E3-oo parameters are hidden when a PM motor control
mode is selected (A1-02 = 5, 6, or 7).
n
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. A control mode for PM motors cannot be selected for motor 2.
No.
E3-01
Note:
L1-01 determines protection from motor overload (oL1) in motor 2 and motor 1.
Setting 0: V/f Control
Setting 1: V/f Control with PG
Setting 2: Open Loop Vector Control
Setting 3: Closed Loop Vector Control
n
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in
Note:
Certain E3-oo parameters might not be visible depending on the control mode.
No.
E3-04
E3-05
E3-06
E3-07
E3-08
E3-09
E3-10
Motor 2 Minimum Output Frequency Voltage
E3-11
E3-12
E3-13
<1> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01).
<3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
<4> Parameter ignored when E3-11 and E3-12 are set to 0.0.
80
Parameter Name
Motor 2 Control Mode Selection
Parameter Name
Motor 2 Max Output Frequency
Motor 2 Max Voltage
Motor 2 Base Frequency
Motor 2 Mid Output Frequency
Motor 2 Mid Output Frequency Voltage
Motor 2 Minimum Output Frequency
Motor 2 Mid Output Frequency 2
Motor 2 Mid Output Frequency Voltage 2
Motor 2 Base Voltage
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Refer to Setting 16: Motor 2 Selection on page 100
Refer to Parameter List on page 235
Setting Range
40.0 to 150.0 Hz
0.0 to 510.0 V
0.0 to [E3-04]
0.0 to [E3-04]
0.0 to 510.0 V
0.0 to [E3-04]
0.0 to 510.0 V
0.0 to [E3-04]
0.0 to 510.0 V
0.0 to 510.0 V
for details on
Setting Range
0 to 3
Figure
1.51.
for details.
<1>
<1>
<1>
0.0 Hz
<1>
0.0 V
<1>
0.0 V
Default
0
Default
<2>
<1> <2>
<2>
<2>
<1> <2>
<2>
<1> <2>
<4>
<3> <4>