1.10 o: Operator Related Settings
Setting 0: ENTER Key Required
The ENTER key must be pressed every time the frequency reference is changed using the digital operator for the drive to
accept the change.
Setting 1: ENTER Key Not Required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital operator.
The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after remaining unchanged
for 5 seconds.
n
o2-06: Operation Selection when Digital Operator is Disconnected
Determines whether the drive will stop when the remote control extension cable of the digital operator is removed in LOCAL
mode or when b1-02 or b1-16 is set to 0. When the operator is reconnected, the display will indicate that it was disconnected.
No.
o2-06
Setting 0: Continue Operation
The operation continues.
Setting 1: Trigger a Fault
The operation stops and triggers an oPr fault. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the digital
operator.
Note:
This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
No.
o2-07
Motor Direction at Power Up when Using Operator
Setting 0: Forward
Setting 1: Reverse
u

o3: Copy Function

These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the
memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, and
same control mode setting.
n
o3-01: Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No.
o3-01
Setting 0: Copy Select (No Function)
Setting 1: INV --> OP READ
Copies all parameters from the drive to the digital operator.
Note:
Set o3-02 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
Copies all parameters from the digital operator to the drive.
Setting 3: OP<-->INV VERIFY
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
n
o3-02: Copy Allowed Selection
Allows and restricts the use of the Copy function.
164
Name
Digital Operator Disconnection Operation
Name
Refer to Copy Function Related Displays on page 222
Name
Copy Function Selection
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Setting Range
0, 1
Setting Range
0, 1
for a description of errors and displays.
Setting Range
0 to 3
Default
1
Default
0
Default
0