d6-06: Field Forcing Limit
Sets the maximum level at which the Field Forcing function can boost the excitation current reference. The value is set as a
percentage of the motor no load current. This parameter does not normally need to be changed.
No.
d6-06
u

d7: Offset Frequency

n
d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed
for Offset frequency 1, 2, and 3 (H1-oo = 44, 45, 46). The selected offset values are added together if multiple inputs are
closed simultaneously. The value is set as a percentage of the Maximum Output Frequency.
Note:
This function can replace the "Trim Control" function (H1-oo = 1C, 1D) of older Yaskawa drives.
No.
d7-01
d7-02
d7-03
Figure 1.49
illustrates the Offset frequency function.
Frequency
reference
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Parameter Name
Field Forcing Limit
Parameter Name
Offset Frequency 1
Offset Frequency 2
Offset Frequency 3
Offset Frequency 1 [d7-01]
(Signed)
Offset Frequency 2 [d7-02]
(Signed)
Offset Frequency 3 [d7-03]
(Signed)
Figure 1.49 Offset Frequency Operation
Setting Range
Setting Range
-100.0 to 100.0%
-100.0 to 100.0%
-100.0 to 100.0%
SFS
Multi-function
input (44) = on
Multi-function
input (45) = on
Multi-function
input (46) = on
1.4 d: Reference Settings
Default
100 to 400%
Default
Frequency
reference after
soft starter
400%
0%
0%
0%
1
73