Operator Programming Errors

u

Operator Programming Error Codes, Causes, and Possible Solutions

An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an
inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not
trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to
an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is causing the oPE.
Digital Operator Display
The drive model selection (o2-04) and the actual capacity of the drive are
not the same.
Digital Operator Display
Parameters were set outside the possible setting range.
Note:
When multiple errors occur simultaneously, other errors are given precedence over oPE02.
Digital Operator Display
• The same function is assigned to two multi-function inputs.
• Excludes "Not used" and "External Fault."
The Up command was set but the Down command was not, or vice versa
(settings 10 vs. 11).
The Up 2 command was set but the Down 2 command was not, or vice versa
(settings 75 vs. 76).
• Run/Stop command for a 2-wire sequence was set (H1-oo = 42), but
Forward/Reverse command (H1-oo = 43) was not.
• "Drive Enable" is set to multi-function input S1 or S2 (H1-01 = 6A or
H1-02 = 6A).
Two of the following functions are set simultaneously:
• Up/Down Command (10 vs. 11)
• Up 2/Down 2 Command (75 vs. 76)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample/Hold (1E)
• Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
The Up/Down command (10, 11) and PID control (b5-01) are enabled
simultaneously.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table 2.12 oPE Codes, Causes, and Possible Solutions
oPE01
Cause
oPE02
Cause
oPE03
Cause

2.6 Operator Programming Errors

Table 2.12
Error Name
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Possible Solutions
Correct the value set to o2-04.
Error Name
Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.
Possible Solutions
Set parameters to the proper values.
Error Name
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01
to H1-08.
Possible Solutions
• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.
Properly set the functions that required for use in combination with other
functions.
Properly set the functions that required for use in combination with other
functions.
• Check if contradictory settings have simultaneously been assigned to the
multi-function input terminals.
• Correct setting errors.
Set b5-01 to 0 to disable control PID or disable the Up/Down command.