A-8 Setting Levels Diagram
This diagram shows all of the setting levels. To move to the Advanced Function Setting Level and Cali-
bration Level, you must enter passwords. Some parameters are not displayed depending on the protect
level setting and the conditions of use.
Control stops when you move from the Operation Level to the Initial Setting Level.
Manual Control
Level
Used to set the MV
manually.
Set the PF Setting parameter to a-m (Auto/Manual).
*1
*2
The No. 1 display will flash when the keys are pressed for 1 s or longer.
Set the PF Setting parameter to pfdp (monitor/setting items).
*3
E5@C-T Digital Temperature Controllers User's Manual (H185)
Starting in manual mode
Power ON
Level changes
automatically.
Press O or
*1
S Key for at least 1 s.
Operation Level
Press O Key for at
least 3 s while a-m is
Used for SPs and other
*2
displayed.
basic settings and
monitoring.
Press S Key
*1
for at least 1 s.
Press O
Key for at
least 1 s.
PID Setting
Parameters for all PID
sets (e.g., PID
constants)
Initial Setting Level
Used to set the input type
and other basic settings.
Release protection and then
enter the password (−169) for
the amoV (Move to Advanced
Function Setting Level)
parameter.
Advanced Function
Setting Level
Advanced settings
Enter the password
(1201) for the Move to
Calibration Level
parameter.
Calibration Level
000
Press O and M Keys
Protect Level
for at least 1 s.
Used to set protection
for operations.
*3
Press S Key.
Program Setting
Press O Key
for less than 1 s.
Parameter and
segment settings for
all programs
Press O Key
for less than 1 s.
Press O Key
for less than 1 s.
Adjustment Level
Level
Adjustment parameters
(e.g., PID constants for
current PID set)
Press O Key for
*2
at least 3 s.
Monitor/Setting
Item Level
Used to display
specified monitor and
setting items.
Control stops.
Press O Key for less
than 1 s (only models
Communications
with communications).
Setting Level
Communications settings
Press O Key for at
least 1 s.
A Appendices
Press O and M Keys
*2
for at least 3 s.
Level
Press O Key
for less than 1 s.
*3
Press S Key.
A - 37
A