In this example, direct/reverse operation, and control period
(heating) parameters are checked.
Direct/reverse operation = or-r (reverse operation)
Control period (heating) = 20 (seconds)
Operating Procedure
• Setting the Control Period (Heating) Parameter
1
Press the M Key several times in the Initial Setting Level to
display cp (Control Period (Heating)).
2
Press the U or D Key to set the value to 20.
The default for a relay output is 20 seconds.
• Setting Direct/Reverse Operation
1
Press the M Key several times in the Initial Setting Level to
display orev (Direct/Reverse Operation).
2
Press the U or D Key to select or-r (Reverse Operation).
The default is or-r (Reverse Operation).
4-6-3
Assigned Output Functions (Assigning Control Outputs Is Not
Supported for Position-proportional Models.)
• Function assignments can be changed by changing the settings for control and auxiliary output
assignments.
• The default function assignments for each output are shown below.
Parameter name
Control Output 1 Assignment
Control Output 2 Assignment
Auxiliary Output 1 Assignment
Auxiliary Output 2 Assignment
Auxiliary Output 3 Assignment
Auxiliary Output 4 Assignment
(E5EC-T/E5AC-T only)
*
If the Controller is equipped with HB/HS alarm detection, it is set by default to detect heater alarms (HA).
Therefore, the alarm 1 function is disabled and the Alarm 1 Type is not displayed. To enable alarm 1, set an
output assignment to alarm 1.
• Refer to page 6-98 for the functions that can be assigned to the outputs.
• Each output is automatically initialized as shown below by changing the control mode between
standard and heating/cooling.
E5@C-T Digital Temperature Controllers User's Manual (H185)
Display
Initial status
out1
Control output
(heating)
out2
Not assigned.
sub1
Alarm 1*
sub2
Alarm 2
sub3
Alarm 3
sub4
Alarm 4
4 Basic Operation
Initial Setting Level
cp
Control Period
(Heating)
20
cp
20
Initial Setting Level
orev
Direct/Reverse
Operation
or-r
orev
or-r
4 - 23