Omron E5AC-T User Manual page 360

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

alma
You can use the integrated alarm to output an OR of alarm 1, alarm 2, alarm 3, alarm 4, the
HB alarm, the HS alarm, the input alarm. Set this parameter to the sum of the codes of the
status for which to output an OR.
Function
The default is 49 (i.e., an OR of alarm 1, the HB alarm, and the HS alarm is output). The
alarm 1 code is 1, the HB alarm code is 16, and the HS alarm code is 32: 1 + 16 + 32 = 49.
Setting
Related Parameters
See
See
Alarm Value 1 to 4 (Operation Level): Page 6-20
MV at Error (Adjustment Level): Page 6-39
HB ON/OFF (Advanced Function Setting Level): Page 6-84
HS Alarm Use (Advanced Function Setting Level): Page 6-94
alsp
This parameter sets whether to use the present SP or the segment SP as the SP that triggers a devia-
tion alarm during ramp segment operation.
Setting
Related Parameters
4-7 Setting Programs (page 4-27)
See
See
E5@C-T Digital Temperature Controllers User's Manual (H185)
Integrated Alarm Assignment
Code
Status
+1
Alarm 1
+2
Alarm 2
+4
Alarm 3
+8
Alarm 4
+16
HB alarm
+32
HS alarm
+64
Input error
Setting range
0 to 255
Alarm SP Selection
Setting range
sp-m: Present SP, tsp: Segment SP
The integrated alarm must be assigned.
Default
49
Alarms 1, 2, 3, and 4 must be assigned.
The Alarm Type parameter must be set to 1, 2, 3, 4,
5, 6, 7, 14, or 15.
Default
sp-m
6 Parameters