• These parameters set the output periods. Set the control periods taking the control
characteristics and the electrical life of the relay into consideration.
• For standard control, use the Control Period (Heating) parameter. The Control Period
Function
(Cooling) parameter cannot be used.
• When the heating or cooling control output is a linear current output, the Control Period
(Heating or Cooling) parameter cannot be used.
• For heating/cooling control, the control period can be set independently for heating and
cooling. The Control Period (Heating) parameter is used for the heating control output,
and the Control Period (Cooling) parameter is used for the cooling control output.
Parameter name
Control Period
Setting
(Heating)
Control Period
(Cooling)
Related Parameters
See
See
PID ON/OFF (Initial Setting Level): Page 6-63
E5@C-T Digital Temperature Controllers User's Manual (H185)
Control Period (Heating)
Control Period (Cooling)
Setting range
0.1, 0.2, 0.5, 1 to 99
0.1, 0.2, 0.5, 1 to 99
The cooling control output and heating control
output must be assigned to relay or voltage
outputs (for driving SSR).
The control must be set to 2-PID control.
For the Control Period (Cooling) parameter, the
control must be set to heating/cooling control.
Unit
Seconds
20 for relay output
2 for voltage output (for driving SSR)
Seconds
20 for relay output
2 for voltage output (for driving SSR)
6 Parameters
Default
6 - 65