6 Parameters
s-hc
• This parameter selects standard control or heating/cooling control.
• If heating/cooling control is selected for the E5CC-T when there is only one control output,
the auxiliary output 2 terminal (SUB2) is assigned as the control output for cooling.
Function
• If heating/cooling control is selected for the E5EC-T/E5AC-T when there is only one
control output, the auxiliary output 4 terminal (SUB4) is assigned as the control output for
cooling.
Note: If standard control is selected, set the Control Output 1 Assignment to o (control output
(heating)) for either direct (cooling) or reverse (heating) operation.
Setting
Related Parameters
See
See
MV Monitor (Heating) (Operation Level): Page 6-14
MV Monitor (Cooling) (Operation Level): Page 6-15
Dead Band (Adjustment Level): Page 6-37
Hysteresis (Heating) and Hysteresis (Cooling) (Adjustment Level): Page 6-38
Control Period (Heating) and Control Period (Cooling) (Initial Setting Level): Page 6-65
Control Output 1 and 2 Assignment (Advanced Function Setting Level): Page 6-97
Auxiliary Output 1 to 4 Assignment (Advanced Function Setting Level): Page 6-98
6 - 64
Standard or Heating/Cooling
Setting range
stnd: Standard, h-c: Heating/cooling
A Standard Model must be used.
Default
stnd
E5@C-T Digital Temperature Controllers User's Manual (H185)