Parameter Operation Lists - Omron E5AC-T User Manual

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

A Appendices
A-6 Parameter Operation Lists
A-6-1
Operation Level
Parameter
Characters
Process Value (1) (2)
Set Point (1) (2)
a-m
Auto/Manual Switch
pgsg
Program No. Monitor/
Segment No. Monitor
prg
Program Number
hold
Hold
seg
Segment Number
stbm
Remaining Standby Time
Monitor
prgt
Elapsed Program Time
Monitor
rptm
Program Execution
Repetitions Monitor
ct1
Heater Current 1 Value
Monitor
ct2
Heater Current 2 Value
Monitor
lcr1
Leakage Current 1
Monitor
lcr2
Leakage Current 2
Monitor
r-r
Run/Reset (program)
o
MV Monitor (Heating)
c-o
MV Monitor (Cooling)
V-m
Valve Opening Monitor
A - 18
Setting (monitor) value
Temperature: According to indication range for each
sensor.
Analog: Scaling lower limit
−5% FS to Scaling upper limit +5% FS
SP lower limit to SP upper limit
During Program Operation
Program number: 0 to 7
Segment number: 0 to 31
0 to 7
ON or OFF
0 to 31
Standby time in hours and minutes: 0.00 to 99.59
Standby time in days and hours: 0.00 to 99.23
0.00 to 99.59
0 to 9,999
0.0 to 55.0
0.0 to 55.0
0.0 to 55.0
0.0 to 55.0
Run or Reset
−5.0 to 105.5 (standard)
0.0 to 105.0 (heating/cooling)
0.0 to 105.0
−10.0 to 110.0
Display
Auto/Manual
on, off
run, rst
E5@C-T Digital Temperature Controllers User's Manual (H185)
Default
Unit
EU
0
EU
Automatic
None
0.00
None
0
None
OFF
None
None
Hours and
minutes, or
days and
hours
Hours and
minutes, or
minutes and
seconds
Repetitions
A
A
A
A
RST
None
0.0
%
0.0
%
0.0
%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ec-tE5cc-t

Table of Contents