Omron E5AC-T User Manual page 392

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

Number of
outputs
Transfer output
Output
specifications
Potentiometer input
Setting method
Indication method
E5CC-T
E5EC-T/E5AC-T
Bank switching function
Other functions
Ambient temperature
Ambient humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
HB and HS Alarms
(E5@C-T Models with HB and HS Alarms)
Max. heater current
Input current readout
accuracy
Heater burnout alarm
setting range
Heater short alarm
setting range
*1
HB alarms are not detected and the heater power is not measured if the ON time for the control output for
heating is 100 ms or less (30 ms or less if the control period is 0.1 or 0.2 s).
*2
HS alarms are not detected and the leakage power is not measured if the ON time for the control output
for heating is 100 ms or less (35 ms or less if the control period is 0.1 or 0.2 s).
E5@C-T Digital Temperature Controllers User's Manual (H185)
1 (only on models with a transfer output)
4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000
Current output:
±0.3%
Linear voltage output: 1 to 5 VDC, Load: 1 kΩ min., Resolution: Approx. 10,000
±0.3%
100 Ω to 10 kΩ
Digital setting using front panel keys
11-segment digital displays and individual indicators
Number of digits: 4
Character heights: PV: 15.2 mm, SV: 7.1 mm
Character heights: E5EC-T: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
E5AC-T: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Three display levels. Contents: PV, SP, program No. and segment No., remaining
None
Manual output, heating/cooling control, loop burnout alarm, other alarm functions,
heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT,
MV limiter, input digital filter, robust tuning, PV input shift, protection functions,
extraction of square root, MV change rate limit, logic operations, temperature
status display, moving input average, and display brightness setting
−10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C
(with no condensation or icing)
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Installation Category II, Pollution Degree 2 (IEC 651010-1 compliant)
50 A AC
±5% FS ±1 digit max.
0.1 to 49.9 A (0.1 A units)
0.0 A:
Heater burnout alarm output turns OFF.
50.0 A:
Heater burnout alarm output turns ON.
*1
Min. detection ON time
:
0.1 to 49.9 A (0.1 A units)
0.0 A:
Heater short alarm output turns ON.
50.0 A:
Heater short alarm output turns OFF.
*2
Min. detection OFF time
:
segment time, or MV (valve opening)
30 ms for a control period of 0.1 s or 0.2 s
100 ms for a control period of 0.5 s or 1 to 99 s
35 ms for a control period of 0.1 s or 0.2 s
100 ms for a control period of 0.5 s or 1 to 99 s
A Appendices
A
A - 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ec-tE5cc-t