6 Parameters
pmvd
• The Direct Setting of Position Proportional MV parameter can be set to ON to enable
specifying the valve open with the MV at Stop, MV at PV Error, and Manual MV
parameters.
Function
Setting
Related Parameters
See
See
MV at Reset and MV at Error (Adjustment Level): Page 6-39
PV/MV (Manual MV) (Manual Control Level): Page 6-53
pvrp
• The change width can be found for PV input values in any set period. Differences with
previous values in each set period are calculated, and an alarm is output if the results
exceed the alarm value.
Function
• The PV rate of change calculation period can be set in units of 50 ms (sampling period).
Setting
Related Parameters
See
See
Process Value/Set Point (Operation Level): Page 6-8
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
6 - 102
Direct Setting of Position
Proportional MV
Setting range
on: Enabled, off: Disabled
PV Rate of Change Calculation
Period
Setting range
1 to 999
Sampling cycle
Close control must be used (Position-proportional
Model).
Default
off
Alarms 1, 2, 3, and 4 must be assigned. The alarm
type must be set to 13.
Unit
Default
20 (1 s)
E5@C-T Digital Temperature Controllers User's Manual (H185)