2 Preparations
E5AC-T
Individual Mounting
+0.8
92
0
• Waterproofing is not possible when group mounting several Controllers.
• The recommended panel thickness is 1 to 5 mm for the E5CC-T, and 1 to 8 mm for E5EC-T, and
E5AC-T.
• Controllers must not be closely mounted vertically. (Observe the recommended mounting space
limits.)
• When two or more Digital Controllers are mounted, make sure that the surrounding temperature does
not exceed the allowable operating temperature specified in the specifications.
*
For E5EC-T models with two control outputs (QQ, QR, CQ, RR, CC, or PR) and 019, 020, 021, or 022
options (shown below), the ambient temperature for group mounting must be 45°C max.
E5EC-T-@@ @ @ @ M-@@@
To mount these models at an ambient temperature of 55°C, install them at the following intervals.
45