al1h
al2h
al3h
al4h
al1l
al2l
al3l
al4l
These parameters are used to set the alarm upper limits and alarm lower limits for alarms for which
upper/lower limits have been selected in Alarm 1 Type to Alarm 4 Type (initial setting level).
• These parameters set the upper limits and lower limits for alarms 1 to 4 of the specified
program number.
• For a temperature input, the decimal point is automatically set according to the selected
Function
sensor. For an analog input, the decimal point is set according to Decimal Point
parameter setting.
Setting
Related Parameters
See
See
Input Type (Initial Setting Level): Page 6-56
Scaling Upper Limit, Scaling Lower Limit, Decimal Point (Initial Setting Level): Page 6-57
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
Alarm 1 to 4 Hysteresis (Initial Setting Level): Page 6-70
Standby Sequence Reset (Advanced Function Setting Level): Page 6-83
Auxiliary Output 1 to 4 Open in Alarm (Advanced Function Setting Level): Page 6-84
Alarm 1 to 4 Latch (Advanced Function Setting Level): Page 6-89
E5@C-T Digital Temperature Controllers User's Manual (H185)
Alarm Upper Limit 1
Alarm Upper Limit 2
Alarm Upper Limit 3
Alarm Upper Limit 4
Alarm Lower Limit 1
Alarm Lower Limit 2
Alarm Lower Limit 3
Alarm Lower Limit 4
Setting range
−1999 to 9999
Alarms 1 to 4 must be assigned.
The alarm 1 to 4 type must be set to 1, 4, or 5.
Unit
Default
EU
0
6 Parameters
6
6 - 21