6 Parameters
a1of
a2of
a3of
a4of
The alarm 1, 2, 3, or 4 output is prevented from turning OFF until after the delay times set in these
parameters have elapsed.
• Set the time for which the OFF delay is to be enabled.
• To disable the OFF delay, set 0.
Function
Setting
Related Parameters
See
See
Alarm 1 to 4 Type (Initial Setting Level): Page 6-66
mant
If this parameter is set to HOLD when control moves from Automatic Mode to Manual Mode,
the final MV from Automatic Mode will be used as the initial manual MV. If this parameter is
set to INT, the setting of the Manual MV Initial Value parameter will be used as the initial
Function
manual MV.
Setting
Related Parameters
See
See
Manual MV Initial Value (Advanced Function Setting Level): 6-93
6 - 92
Alarm 1 OFF Delay
Alarm 2 OFF Delay
Alarm 3 OFF Delay
Alarm 4 OFF Delay
Setting range
0 to 999
Seconds
Manual Output Method
Setting range
hold: HOLD, init: INIT
Alarm 1 must be assigned, and the alarm 1 type
must not be 0, 12, or 13.
Alarm 2 must be assigned, and the alarm 2 type
must not be 0, 12, or 13.
Alarm 3 must be assigned, and the alarm 3 type
must not be 0, 12, or 13.
Alarm 4 must be assigned, and the alarm 4 type
must not be 0, 12, or 13.
Unit
Default
0
Control must be set to 2-PID control.
A Position-proportional Model set to Close Control
with the Direct Setting of Position-proportional MV
parameter set to ON must be used.
Default
hold
E5@C-T Digital Temperature Controllers User's Manual (H185)