Omron E5AC-T User Manual page 366

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

pf
• This parameter sets the function of the PF Key.
Function
• The default is SHFT (Digit Shift).
Setting
OFF: off
RUN: run
RST: rst
R-R: r-r
HOLD: hold
ADV: adv
AT-2: at-2
AT-1: at-1
ATA2: ata2
ATA1: ata1
LAT: lat
A-M: a-m
PFDP: pfdp
SHIFT: shft Digit Shift
*1
The reset operation for a Reset or Reverse Run/Reset setting is implemented by pressing the PF
Key for at least two seconds. The Run operation is implemented by pressing the PF Key for at
least one second.
*2
When AT cancel is specified, it means that auto-tuning is cancelled regardless of the type of
auto-tuning that is currently being executed.
*3
AT-1 or ATA1 can be set for heating/cooling control or position-proportional (floating) control, but
the function is disabled.
*4
Alarms 1 to 4, the HB alarm, and the HS alarm are cancelled.
*5
For details on auto/manual operations using the PF Key, refer to 5-11 Performing Manual
Control.
*
Operation will be performed according to the setting of this parameter when the PF Key is pressed
for at least one second. (This does not apply to the reset operation when Reverse Run/Reset is
set.) If Monitor/Setting Items is selected, the display will switch between monitor/setting items 1 to
5 each time the key is pressed.
*
The PF Key is enabled only when the PF Key Protect parameter is set to OFF.
Related Parameters
See
See
Monitor/Setting Item 1 to 5 (Advanced Function Setting Level): Page 6-106
E5@C-T Digital Temperature Controllers User's Manual (H185)
PF Setting
Set value
Setting
Disabled
RUN
Reset
Reverse Run/Reset
Reverse Hold/Clear
Hold
Advance
100%AT
Execute/Cancel
40%AT
Execute/Cancel
All PID 100% AT
Execute/Cancel
All PID 40% AT Exe-
cute/Cancel
Alarm Latch Cancel
Auto/Manual
Monitor/Setting Item
Function
Does not operate as a function key.
Specifies RUN status.
Specifies Reset status.*1
Specifies reversing operation status between Run and
Reset.*1
Specifies reversing operation status between Hold and
Hold Clear.
Specifies performing advance operation.
Specifies reversing 100% AT Execute/Cancel status.
Specifies reversing 40% AT Execute/Cancel status.
Specifies reversing 100% AT execute/cancel status for all
*2
PID sets.
Specifies reversing 40% AT execute/cancel status for all
*2 *3
PID sets.
Specifies canceling alarm latches.
Specifies reversing Auto/Manual status.
Specifies the monitor/setting item display. Select the
monitor/setting item using the Monitor/Setting Item 1 to 5
parameters (Advanced Function Setting Level).
Operates as a Digit Shift Key when settings are being
changed.
6 Parameters
*2
*2 *3
6
*4
*5
6 - 105