5 Advanced Operations
The following procedure sets the transfer output for an SP range of −50
to 200.
Operating Procedure
• Setting the Transfer Output Type
1
Press the M Key several times in the Initial Setting Level to
display tr-t (Transfer Output Type).
2
Press the U or D Key to select sp-m (present SP).
The default is off.
• Setting the Transfer Output Upper Limit
1
Press the M Key several times in the Initial Setting Level to
display tr-h (Transfer Output Upper Limit).
2
Press the U or D Key to set the value to 200.
The default is 1300.
• Setting the Transfer Output Lower Limit
1
Press the M Key several times in the Initial Setting Level to
display tr-l (Transfer Output Lower Limit).
2
Press the U or D Key to set the value to −50.
The default is −200.