6 Parameters
init
• This parameter returns all parameter settings to their defaults.
• After the initialization, the set value automatically turns OFF.
Function
Setting
fact:
pend
• This parameter sets the pulse width of the program end output.
The setting range is ON or 0.0 to 10.0 s. The default is 0.0 s.
• If ON is set, the output will remain ON until the Run/Reset parameter is changed to Run
Function
during reset status.
on: Output continuously.
Setting
0.0: No output.
0.1 to 10.0
Related Sections
See
See
5-15 Program-related Functions (page 5-53)
Related Parameters
Control Output 1 and 2 Assignment (Initial Setting Level): Page 6-97
Auxiliary Output 1 to 4 Assignment (Initial Setting Level): Page 6-98
s-u
• This parameter sets the unit for the standby time.
Always set this parameter before setting the standby time.
Function
h-m: Hours and minutes
Setting
d-h: Days and hours
Related Parameters
See
See
Standby Time (Adjustment Level): Page 6-34
6 - 82
Parameter Initialization
off:
Initialization is not executed.
Initializes to the factory settings described in the manual.
Program End ON Time
Setting range
Seconds
Standby Time Unit
Setting range
Setting range
Unit
Default
0.0: No output.
Unit
h-m: Hours and minutes
---
E5@C-T Digital Temperature Controllers User's Manual (H185)
Default
off
Default