Omron E5AC-T User Manual page 280

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

pr
• This parameter sets the amount of change per the time unit of the slope for the specified
segment number.
• If this parameter is set to 0, the segment will be a step segment.
Function
Setting
Related Sections
See
See
5-15 Program-related Functions (page 5-53)
Related Parameters
Step Time/Rate of Rise Programming (Initial Setting Level): Page 6-59
Segment n Format (Program Setting Level): Page 6-18
time
• This parameter sets the segment time for the specified segment number.
• This parameter sets the soak segment time for rate of rise programming.
Function
Setting
* The unit is set in the Program Time Unit parameter. (The default is H-M (hours and min-
utes).)
Related Sections
See
See
5-15 Program-related Functions (page 5-53)
Related Parameters
Step Time/Rate of Rise Programming (Initial Setting Level): Page 6-59
Segment n Format (Program Setting Level): Page 6-18
E5@C-T Digital Temperature Controllers User's Manual (H185)
Segment n Slope (n = 0 to 31)
Setting range
0 to 9999
Segment n Time (n = 0 to 31)
Setting range
0.00 to 99.59
Hours and minutes, or minutes and seconds
The Displayed Segment Selection parameter must
not be set to END. The Step Time/Rate of Rise
Programming parameter must be set to Rate of
Rise. The Segment Type parameter must be set to
Ramp.
Unit
Default
EU
0
The Display Segment Selection parameter must not
be set to END. The Step Time/Rate of Rise
Programming must be set to Step Time, or the Step
Time/Rate of Rise Programming must be set to
Rate of Rise and the Segment Type parameter must
be set to Soak.
Unit
6 Parameters
Default
0.00
6 - 19
6