Omron E5AC-T User Manual page 39

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

2 Preparations
E5EC-T/E5AC-T
E53-COV24
Terminal Cover
Waterproof packing
Mounting to the Panel
(1) For waterproof mounting, waterproof packing must be installed on the Controller.
Waterproofing is not possible when group mounting several Controllers. Waterproof
packing is not necessary when there is no need for the waterproofing function.
(2) Insert the E5EC-T/E5AC-T into the mounting hole in the panel.
(3) Push the Adapter from the terminals up to the panel, and temporarily fasten the
E5EC-T/E5AC-T.
(4) Tighten the two fastening screws on the Adapter. Alternately tighten the two screws little by
little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
Mounting the Terminal Cover
Slightly bend the E53-COV24 Terminal Cover to attach it to the terminal block as shown in the following
diagram. The Terminal Cover cannot be attached in the opposite direction.
2 - 6
Adapter
Panel
*
Enlarged Illustration of Terminal Section
Adapter
The Terminal Cover is provided only with the
following models: E5@C-T@@@@5M-@@@.
Slightly bend the
E53-COV24
Terminal Cover in
the direction shown
by the arrows to
attach it to the
terminal block.
E5@C-T Digital Temperature Controllers User's Manual (H185)
E53-COV24
Terminal Cover*