c-o
This parameter is used to monitor the manipulated variable for the cooling control output during opera-
tion.
• During heating/cooling control, the manipulated variable on the control output (cooling) is
monitored.
• This parameter is masked by default and the manipulated variable is not displayed.
Function
Monitor
Related Parameters
See
See
Standard or Heating/Cooling (Initial Setting Level): Page 6-64
Parameter Mask Setting (Advanced Function Setting Level): Page 6-110
v-m
• This parameter is used to monitor the valve opening for position-proportional control.
• The valve opening can be monitored if a potentiometer is connected and motor calibration
is executed.
Function
Position-proportional control
Monitor
Related Parameters
See
See
Motor Calibration (Initial Setting Level): Page 6-76
E5@C-T Digital Temperature Controllers User's Manual (H185)
MV Monitor (Cooling)
Control
Monitor range
Heating/cooling
0.0 to 105.0
Valve Opening Monitor
Control
The control system must be set to heating/cooling
control.
Unit
%
A Position-proportional Model must be used.
Monitor range
Unit
−10.0 to 110.0
%
6 Parameters
6
6 - 15