6 Parameters
hsu
• Set this parameter to use HS alarms.
Function
on: Enabled, off: Disabled
Setting
hsl
• When this parameter is set to ON, the HS alarm is held until any of the following
conditions is satisfied.
Function
• Output is turned OFF when switching to the Initial Setting Level, Communications Setting
Level, Advanced Function Setting Level, or Calibration Level.
Setting
Related Parameters
See
See
HS Alarm Use (Advanced Function Setting Level): Page 6-94
Event Input Assignment 1 to 6 (Initial Setting Level): Page 6-74
HB ON/OFF (Advanced Function Setting Level): Page 6-84
PF Setting (Advanced Function Setting Level): Page 6-105
6 - 94
HS Alarm Use
Setting range
HS Alarm Latch
a The HS alarm current is set to 50.0 A.
b The power is cycled.
c The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
d The latch is cancelled by an event input.
(Event Input Assignment 1 to 6 = LAT: Alarm Latch Cancel)
Setting range
on: Enabled, off: Disabled
HB and HS alarms must be supported.
Default
on
HB and HS alarms must be supported.
The HS Alarm Use parameter must be set to ON.
Default
off
E5@C-T Digital Temperature Controllers User's Manual (H185)