Omron E5AC-T User Manual page 128

E5xc-t series digital temperature controllers programmable type
Hide thumbs Also See for E5AC-T:
Table of Contents

Advertisement

Setting Example
The following example shows how to set 0.40.
Operating Procedure
1
Specify a segment number for the Display Segment Selection
parameter and press the M Key several times to select the
Segment Time parameter.
2
Press the U or D Key to set 0.40.
The default is 0.00.
Setting the PID Set No. Parameter
This parameter specifies the PID set to use for the program.
Related Parameters
Parameter name
PID Set No.
Setting Example
The following example shows how to set the PID set number to 2.
Operating Procedure
1
Press the M Key several times in the Program Setting Level to
select the PID Set No. parameter.
2
Press the U or D Key to set 2.
The default is 1.
Setting the Alarm Value Parameter
Set the alarm value for the alarm to use.
Related Parameters
Parameter name
Alarm Value 1 to 4
E5@C-T Digital Temperature Controllers User's Manual (H185)
Display
Setting range
pid
0: Automatic selection
1 to 8: PID set number
Display
Setting range
al-1 to 4
-1999 to 9999
4 Basic Operation
Program Setting Level
time
0.00
time
0.40
Default
Level
1
Program Setting Level
Program Setting Level
pid
pid
Default
Level
0
Program Setting Level
Segment 1
Time
4
PID Set No.
1
2
4 - 43