Parameter Operation Lists - Omron E5CN User Manual

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Parameter Operation Lists

Universal input: Controllers with Thermocouple/Resistance Thermometer Universal Inputs
Analog input: Controllers with Analog Inputs
Operation Level
Parameters
Characters
Process Value
Set Point
a-m
Auto/Manual Switch
m-sp
Multi-SP Set Point
Setting
sp-m
Set Point During SP
Ramp
ct1
Heater Current 1
Value Monitor
ct2
Heater Current 2
Value Monitor
lcr1
Leakage Current 1
Monitor
lcr2
Leakage Current 2
Monitor
prst
Program Start
sktr
Soak Time Remain
r-s
RUN/STOP
al-1
Alarm Value 1
al1h
Alarm Value Upper
Limit 1
al1l
Alarm Value Lower
Limit 1
al-2
Alarm Value 2
al2h
Alarm Value Upper
Limit 2
al2l
Alarm Value Lower
Limit 2
al-3
Alarm Value 3
al3h
Alarm Value Upper
Limit 3
al3l
Alarm Value Lower
Limit 3
o
MV Monitor (Heat-
ing)
c-o
MV Monitor (Cool-
ing)
266
Setting (monitor) value
Temperature: According to
indication range for each sen-
sor.
Analog: Scaling lower limit
−5% FS to Scaling upper limit
+5% FS
SP lower limit to SP upper
limit
0 to 3
SP lower limit to SP upper
limit
0.0 to 55.0
0.0 to 55.0
0.0 to 55.0
0.0 to 55.0
RSET, STRT
0 to 9999
RUN/STOP
−1999 to 9999
−1999 to 9999
−1999 to 9999
−1999 to 9999
−1999 to 9999
−1999 to 9999
−1999 to 9999
−1999 to 9999
−1999 to 9999
−5.0 to 105.5 (standard)
0.0 to 105.0 (heating/cooling)
0.0 to 105.0
Display
Default
0
0
rset, strt RSET
run, stop
Run
0
0
0
0
0
0
0
0
0
Appendix
Unit
Set value
EU
EU
None
EU
A
A
A
A
None
min or h
None
EU
EU
EU
EU
EU
EU
EU
EU
EU
%
%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-uE5anE5en

Table of Contents