Setting Output Specifications
Direct/Reverse
orev
Operation
or-r
Operation Level
PV/SP
C
30
0
Move to Ad-
amov
vanced Function
Setting Level
0
3-5-3

Assigned Output Functions

Example: E5CN
Parameter name
Symbol
out1
Control Output 1
Assignment
out2
Control Output 2
Assignment
sub1
Auxiliary Output 1
Assignment
sub2
Auxiliary Output 2
Assignment
44
5. Select the Direct/Reverse Operation parameter by pressing the M Key.
The default is or-r (reverse operation). To select or-d (direct opera-
tion), press the U Key.
6. To return to the operation level, press the O Key for at least one second.
7. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key.
• Function assignments can be changed by changing the settings for con-
trol and auxiliary output assignments.
• The default function assignments for each output are shown below.
Parameter name
Control Output 1 Assignment
Control Output 2 Assignment
Auxiliary Output 1 Assignment
Auxiliary Output 2 Assignment
Auxiliary Output 3 Assignment
(E5AN/EN only)
• Each output is automatically initialized as shown below by changing the
control mode.
Without control output 2
Standard
Control output
(heating)
Not assigned.
(See note 1.)
Alarm 1
(See note 2.)
Alarm 2
(See note 3.)
Note
(1) There is no control output 2 and no parameter assignment is displayed
for that output.
(2) The Auxiliary Output 1 Assignment parameter becomes the program end
output unless the Program Pattern parameter is set to OFF.
(3) For the E5AN/EN, the Auxiliary Output 3 Assignment parameter is set as
the control output for cooling. (The Auxiliary Output 2 Assignment param-
eter is set for alarm 2).
Symbol
out1
out2
sub1
sub2
sub3
Heating/cooling
Control output
Control output
(heating)
(heating)
Not assigned.
Not assigned.
(See note 1.)
Alarm 1
Alarm 1
(See note 2.)
(See note 2.)
Control output
Alarm 2
(cooling)
(See note 3.)
Section 3-5
Initial status
Control output (heating)
Not assigned.
Alarm 1
Alarm 2
Alarm 3
With control output 2
Standard
Heating/cooling
Control output
(heating)
Control output
(cooling)
Alarm 1
(See note 2.)